Microgrid & Energy Storage · Engineered in Shenzhen
STS-400HC — front view
STS-400HC — additional view 2
1 / 2
Static Transfer Switches (STS)

STS-400HC 400 kVA Static Transfer Switch

400 kVA STS · 0 ms active transfer · 20 ms passive transfer

  • Active transfer 0 ms; passive transfer 20 ms typical, under 4 ms on custom build
  • Transfers only when the destination source is within window — no collapse under load
  • Handles grid-to-inverter transfer and grid synchronisation
  • 440 × 420 × 320 mm, 35 kg — cabinet mount, no floor space needed
  • IP5x, −30 to +60 °C — fits an outdoor enclosure
Product introduction

Overview & fit.

The STS-400HC is a 400 kVA static transfer switch that moves a load between two AC sources — typically the grid and a PCS output — without a mechanical break. Active transfer is 0 ms; passive transfer is 20 ms typical, and a custom build can reach under 4 ms.

01What it does

Fast thyristor switching, high-precision grid sensing and a logic controller handle both grid-to-inverter transfer and grid synchronisation. The unit measures both sources continuously and only transfers when the destination is within window, which prevents transferring onto a source that would immediately collapse under load.

02Where it fits

  • Microgrids that must hold a critical load through a grid outage
  • Storage systems where the PCS needs a defined grid-switch step
  • Sites with voltage ride-through requirements on both sources
  • Industrial processes where a 20 ms interruption is tolerable but a 200 ms one is not
GRID A · GRID Btwo sourcesSTSSTS-400HCCRITICAL LOADtransfer < 4 msSYSTEM POSITIONBidirectional power flow shown schematically — actual topology depends on site design
Where the STS-400HC sits in a typical system

03Why this model

At 440 × 420 × 320 mm and 35 kg it mounts in a cabinet rather than needing its own floor space, and IP5x protection with a −30 to +60 °C range means it can sit in an outdoor enclosure. Eight digital inputs and eight outputs let it interlock with the PCS and the breaker without extra hardware.

Technical data

Full specifications.

AC input / output
Rated power400 kVA
Rated voltage230 / 400 Vac (−20% / +15%)
Rated frequency50 / 60 Hz (±5 Hz)
Maximum power440 kVA
Maximum current660 A
Switching performance
Active transfer0 ms
Passive transfer20 ms typical
Transfer time at PCC<10 ms
General
Protection ratingIP5x
Operating temperature−30 to +60 °C
Humidity0–100%
CoolingThermostatic forced air
Maximum altitude4000 m (derating above 3000 m)
CommunicationRS485 ×3 · Modbus TCP · CAN · 4G · DI 8 · DO 8
Dimensions (W×H×D)440 × 420 × 320 mm
Weight≤35 kg

Source: published specification for STS-400HC. Confirm project-specific limits with our engineers before final sizing.

Model-specific documents

Datasheet, GA drawing & terminal schedule.

Issued on request for STS-400HC — tell us the model and destination country and we will send the current revision.

Related

You may also need.

BAC125K950C
BAC125K950C

BAC125K950C 125 kW Bidirectional PCS (All-SiC)

125 kW all-SiC PCS · 600–950 Vdc battery · 98.8% peak efficiency

BIDC1500100
BIDC1500100

BIDC1500100 125 kW Bidirectional DC/DC Module

125 kW bidirectional DC/DC · 600–1500 V · up to 40 units in parallel

IMDC100100
IMDC100100

IMDC100100 5 kW Isolated Bidirectional DC/DC Module

5 kW isolated DC/DC · 200–420 Vdc bus · 32 units in parallel

Ready to size your system?

Send us your DC bus or battery voltage, PV array size, load profile and grid conditions — we will confirm the configuration and parallel scheme.