BIDC1500100 125 kW Bidirectional DC/DC Module
125 kW bidirectional DC/DC · 600–1500 V · up to 40 units in parallel
- 125 kW continuous through one non-isolated bidirectional buck-boost stage
- 600–1500 V on both ports, with a 600–1400 V MPPT input
- Up to 40 units in parallel, under 7% current imbalance in CV mode
- Constant current, constant voltage, constant power and PV mode; dark start supported
- 350 × 85 × 585 mm, under 17 kg, forced-air cooled, IP00
- RS-485 / CAN / optional Ethernet with published Modbus and CAN protocols; external 24 V auxiliary supply required
Overview & fit.
The BIDC1500100 is a 125 kW non-isolated bidirectional DC/DC module built around a buck-boost stage. Port A connects to a 600–1500 V DC bus; Port B connects to a 600–1500 V battery cluster or, in PV mode, to a 600–1400 V PV string. The user manual positions it between a shared DC busbar and PV arrays or battery clusters in DC-coupled systems.
01What it does
One power stage handles constant-current, constant-voltage and constant-power operation in both directions: charging runs from Port A to Port B, discharging from Port B to Port A. A single MPPT input tracks PV strings between 600 and 1400 V. Dark start is supported — with the storage system shut down, the module can establish the DC bus voltage at a current capacity of 20 A (User Manual V3.0, Section 2.4). Commanded current changes respond in under 5 ms over a 10–90% amplitude step.

02Where it fits
Up to 40 units can operate in parallel on a shared DC bus with automatic current sharing and less than 7% current imbalance in constant-voltage mode (Section 2.3). The 350 × 85 × 585 mm chassis is screw-fastened into racks, is rated IP00 and is cooled by three front-mounted fans. It requires an external 24 V ±1 V auxiliary supply drawing less than 65 W — both are part of the cabinet design, not of the module.

03Why this model
Power relays, fuses and a digital controller are integrated, and the module reports operating status and measured electrical values over RS-485 or CAN, with Ethernet optional. Modbus and CAN protocol documents are published separately. Protection covers reverse connection, over- and under-voltage, over-current, over-temperature, communication loss, fan error and emergency power off (Section 3). Safety standards quoted in the manual are IEC 62477 and UL 1741, with a calculated MTBF of 400,000 hours.

Full specifications.
| DC Bus Side (Port A) | |
| Rated voltage (VANOM) | 1250 V |
| Operating voltage range | 600–1500 V |
| Over-voltage protection | 1560 ±20 V (default, configurable) |
| Under-voltage protection | 550 ±20 V (default, configurable) |
| Rated current (IANOM) | 100 A |
| Current measurement accuracy | 1.5% F.S. |
| Voltage measurement accuracy | 0.5% |
| Rated operating point voltage control accuracy | 0.5% (droop control enabled) |
| Battery Side (Port B) | |
| Rated voltage (VBNOM) | 1250 V |
| Operating voltage range | 600–1500 V |
| Over-voltage protection | 1560 ±20 V (default, configurable) |
| Under-voltage protection | 550 ±20 V (default, configurable) |
| Rated current (IBNOM) | 100 A |
| Over-current protection | 105–120%: trip after 20 s · >120%: trip within 0.1 s |
| Maximum continuous power | 125 kW |
| Current ripple RMS | ≤5% IBNOM |
| Rated operating point voltage measurement accuracy | 0.5% |
| Rated operating point voltage control accuracy | 0.5% (droop control enabled) |
| Current measurement accuracy | 0.4% |
| Rated operating point current control accuracy | 0.5% |
| PV Parameters | |
| Maximum DC input voltage | 1500 V |
| Maximum input current per MPPT | 90 A |
| Maximum short-circuit current per MPPT | 100 A |
| MPPT voltage range | 600–1400 V |
| MPPT quantity | 1 |
| Efficiency | |
| Maximum efficiency | ≥99.2% |
| CEC efficiency | ≥99% |
| Auxiliary Power Supply | |
| Auxiliary supply voltage | 24 V ±1 V |
| Auxiliary supply power | <65 W |
| Protection | |
| Fuse | Integrated · ≥100 kA, ≥1500 Vdc, L/R ≥3 ms |
| Short-circuit protection | Integrated · input–output port short circuit |
| Over-temperature protection | Integrated · threshold settable via communication |
| Communication fault protection | Integrated · default 0.5 s timeout, settable via communication |
| Mechanical | |
| Dimensions (W×H×L) | 350 × 85 × 585 mm (excluding ear brackets) |
| Weight | <17 kg |
| Cooling | Forced air cooling |
| Protection rating | IP00 |
| Installation | Screw fastening |
| Environment | |
| Operating temperature | −25 to 45 °C (derated 45–55 °C, no condensation) |
| Storage temperature | −40 to 70 °C (no condensation) |
| Operating relative humidity | 5–85% |
| Operating altitude | 4000 m (derated above 3000 m) |
| Noise | ≤75 dB at <30 °C ambient · ≤80 dB maximum |
| Pollution degree | PD2 |
| Vibration and shock | Operating: IEC 60721-3-3, 3M12 · Transport: IEC 60721-3-2, 2M5 |
| Communication & Functions | |
| Communication | RS-485, CAN, Ethernet (optional) |
| Operating modes | Constant current, constant voltage, constant power, PV mode |
| Current dynamic response | <5 ms (10–90% amplitude) |
| Dark start | Supported |
| Parallel capability | Up to 40 units in parallel |
| Current imbalance in CV mode | <7% |
| Safety & Compliance | |
| Withstand voltage | Basic insulation 3.2 kV · reinforced 4.4 kV (50/60 Hz, 60 s) |
| Insulation locations | Basic: input–output, input/output–chassis · Reinforced: input and output to communication and auxiliary supply interfaces |
| Overvoltage category | OV II |
| Certification standards | IEC 62477, UL 1741 |
| EMI | IEC 61000-4, FCC Part 15 Class A (DC radiation test only) |
| EMS | IEC 61000-2 |
| Service Life | |
| Design life | 20 years (fan life maintained or replaced per operating conditions) |
| Calculated MTBF | 400,000 hours (Telcordia SR332 Issue 3) |
Source: BIDC1500100 User Manual V3.0, Technical Specifications. Confirm project-specific limits with our engineers before final sizing.