PV + Storage + Diesel Hybrid for Commercial Sites
One cabinet holds the PCS, MPPT, EMS and transfer switch — grid-tied, with the diesel absorbed into the control logic.
A factory with a roof full of PV, a diesel backup set and a grid connection usually ends up with three systems that do not talk to each other. The PV inverter exports when it should be charging, the diesel starts on a timer rather than on need, and nobody knows which source is cheaper at 14:00 on a Tuesday.
Why one cabinet instead of three boxes
When the PCS, the MPPT and the transfer switch are designed as one unit, the transfer decision is made by the same controller that knows the battery state. There is no negotiation over a Modbus link between three vendors, and no scenario where the PCS is exporting to the grid while the diesel is running to charge the battery. The MSP series packs all of it into a single 1350 × 2200 × 850 mm enclosure.
The control logic that matters
- Anti-backflow caps export at the interconnection limit instead of tripping the main breaker
- Peak shaving charges from PV at midday and discharges into the afternoon peak, so the demand charge falls without cycling the battery twice
- Genset hybrid keeps the diesel at a healthy load and puts surplus into the battery rather than into heat
- SOC balancing across parallel cabinets stops one bank from carrying the others
What it looks like on site
Three cabinets parallel to 1.5 MVA. Each cabinet carries 500 kVA continuous and 550 kVA peak, tolerates 100% load unbalance on the off-grid output, and rides a 1.25 × overload for 300 ms — enough to start a large motor without dropping the rest of the plant. The 800 A bypass allows maintenance without shutting the site down.
What goes on site.
| Integrated cabinet | |
| Model | MSP250HCG2 / MSP375HCG2 / MSP500HCG2 |
| Contents | PCS, 4 × MPPT, EMS, PCM transfer switch, AC/DC distribution |
| Parallel | Up to 3 cabinets, 1.5 MVA maximum |
| Grid transfer | Active 0 ms, passive <10 ms |
| PV input | |
| Voltage window | 200–950 V open circuit |
| MPPT range | 600–900 V |
| Power per channel | 120 kW × 4 |
| Battery | |
| Voltage range | 680–900 V nominal, 950 V maximum |
| Load behaviour | |
| Overload | 1.1 × for 100 s, 1.25 × for 300 ms |
| Unbalance tolerance | 100% on the off-grid output |
| Efficiency | >99.3% system level |