MSP500HCG2 500 kVA Hybrid Solar-Storage Cabinet

500 kVA all-in-one · PCS + 4 MPPT + EMS + transfer · 0 ms active / under 10 ms passive switching

  • PCS, four MPPT channels, EMS and transfer in one 500 kVA cabinet
  • Multi-channel DC coupling with charging efficiency above 99.3%
  • Diesel genset hybrid operation and grid-forming capability
  • Grid-tied/off-grid transfer: 0 ms active, under 10 ms passive (User Manual V2.0)
  • Built-in anti-backflow, self-consumption, peak shaving and valley filling
  • Up to 3 units in parallel; all-in-one design for fast deployment and simple commissioning
Product introduction

Overview & fit.

The MSP500HCG2 is a 500 kVA all-in-one cabinet that integrates PCS, four MPPT channels, EMS, grid-tied/off-grid transfer and AC/DC distribution in one enclosure. It is designed for PV + storage + diesel microgrids where sources and loads would otherwise be spread across several separately specified boxes.

01What it does

On the DC side it accepts 680–900 V battery banks and four PV arrays of up to 120 kW each, tracking between 600 and 900 V. On the AC side it delivers 500 kVA continuous and 550 kVA peak. Grid-tied/off-grid transfer is quoted in the user manual as 0 ms active and under 10 ms passive. The on-board EMS runs SOC balancing, peak shaving, self-consumption, anti-backflow and diesel genset hybrid control; external EMS dispatching is available as an option.

MSP500HCG2 — Typical PV + storage + diesel microgrid — the cabinet sits between the sources and site loads
Typical PV + storage + diesel microgrid — the cabinet sits between the sources and site loads

02Where it fits

  • Photovoltaic-storage-diesel microgrids and islanded sites
  • Backup and emergency power for mines and remote operations
  • Construction sites, oilfield pumping and field operations
  • C&I sites needing peak shaving, self-consumption and anti-backflow control
MSP500HCG2 — Front-service access during factory commissioning
Front-service access during factory commissioning

03Why this model

Because the PCS, MPPT and transfer switch are integrated in one cabinet, the transfer logic is coordinated inside the unit rather than negotiated over a communications link between separate vendors. Up to three cabinets can be paralleled and an 800 A bypass is fitted (User Manual V2.0, Section 3.1). Basic dispatch is available from the on-board EMS; a separate microgrid EMS can be added where the site requires it.

MSP500HCG2 — Up to three cabinets on one AC bus; 800 A bypass fitted (User Manual V2.0, Section 3.1)
Up to three cabinets on one AC bus; 800 A bypass fitted (User Manual V2.0, Section 3.1)
Technical data

Full specifications.

Battery
Maximum battery voltage950 V
Minimum battery voltage680 V
Rated battery voltage range680–900 V
Maximum battery current200 A × 4
PV
PV power120 kW × 4
Maximum PV voltage950 V
Minimum PV voltage200 V
Rated MPPT voltage range600–900 V
Maximum input current200 A × 4
AC side — grid-tied
Rated power500 kVA
Rated current724 A
Rated grid voltage400 / 230 V
Grid voltage range−20% / +15%
Grid unbalance125%
Grid frequency range50 Hz (47–52) / 60 Hz (57–62)
Current harmonics<3% above 30% load
Power factor−1 to 1
AC side — off-grid
Rated output power500 kVA
Maximum output power550 kVA
Rated output current724 A
Maximum output current796.4 A
Rated voltage400 / 230 V
Output voltage harmonics<2% on resistive load
Unbalance100%
Frequency range50 / 60 Hz
Output overload (current)Above 1.1 × Ie up to 1.25 × Ie: 100 s; above 1.25 × Ie: 300 ms (Ie = rated output current)
System
Grid-connected/off-grid switching timeActive 0 ms · passive <10 ms
Parallel units3 (max)
EMS functionsSOC balancing · peak shaving & valley filling · self-consumption · excess power to grid · anti-backflow · diesel genset hybrid · cloud platform
Isolation transformerNone (supports transformer startup addition)
Bypass function800 A
Protection levelIP20
Dimensions (W×H×D)1350 × 2200 × 850 mm
Weight≈850 kg
Temperature range−30 to +60 °C (derating at 45 °C)
Humidity range10–95%
Cooling methodAir cooling
Altitude4000 m (derating above 2000 m)

Source: MSP500HCG2 User Manual V2.0, Section 3.1. Confirm project-specific limits with our engineers before final sizing.

Dimensional drawing

Dimensions & footprint.

MSP500HCG2 — dimensional drawing
MSP500HCG2 — front, side and top view; all dimensions in mm. Source: User Manual V2.0, Section 2.3.
Terminal layout

Wiring ports.

MSP500HCG2 — terminal and port layout
PV inputs PV1–PV4 (left), battery inputs BAT1–BAT4 (right), GRID and LOAD breakers below. Source: User Manual V2.0, Section 4.
Model-specific documents

Datasheet, GA drawing & terminal schedule.

Issued on request for MSP500HCG2 — tell us the model and destination country and we will send the current revision.

Related

You may also need.

BAC125K950C
BAC125K950C

BAC125K950C 125 kW Bidirectional PCS (All-SiC)

125 kW all-SiC PCS · 600–950 Vdc battery · 98.8% peak efficiency

BIDC1500100
BIDC1500100

BIDC1500100 125 kW Bidirectional DC/DC Module

125 kW bidirectional DC/DC · 600–1500 V · up to 40 units in parallel

IMDC100100
IMDC100100

IMDC100100 5 kW Isolated Bidirectional DC/DC Module

5 kW isolated DC/DC · 200–420 Vdc bus · 32 units in parallel